| standard |
|
| GB/T12706.1-2002,GB/T19666-2005 |
|
| Using |
|
The product applies to rated voltage 0.6/1 kV, confess to convey power distribution use of being able to in 50 Hz circuits. |
|
| |
|
| Operating characteristic |
|
|
1、Maximal temperature of Cable conductor is 90℃.
2、In short circuit (max. 5s) cable conductor
Maximum temperature does not exceed 250℃.
3、Cable laying Environmental temperature is not
lower than 0℃, the minimal bending radius is not
smaller than 10 times of cable outside diameter. |
|
| |
|
|
|
|
|
|
|
mono-core |
mull-cores |
|
Non armoured |
Armoured |
Non armoured |
Armoured |
|
20D |
15D |
15D |
12D |
|
| Note:D is the diameter of cable. |
|
| Type |
|
Type |
Name |
Using range |
|
YJV
VLV |
Cross-linked polyethylene
insulation PVC Sheath power cable |
Lay down is in interior、Tunnel and duct,
cable can not bear pressure and the
machinery outside force effect. |
|
YJV22
VLV22 |
Cross-linked polyethylene
insulation double-tape armour
PVC Sheath power cable |
Lay down is in interior, tunnel and burying soil straightly, cable can bear pressure
and other outside force effect. |
|
YJV32
VLV32 |
Cross-linked polyethylene
insulation steel wire Armour
PVC Sheath power cable |
Lay down is in interior, mine and water,
cable can bear pulling force suitable. |
|
YJV42 VLV42 |
Cross-linked polyethylene
insulation thick steel wire
Armour PVC Sheath power cable |
Lay down is in interior, mine and water,
cable can bear bigger pulling force. |
|
Z-YJV
Z-VLV |
Cross-linked polyethylene
insulation PVC Sheath flame
retardant power cable |
Lay down is in interior、Tunnel and
duct,cable can not bear pressure and the
machinery outside force effect. |
|
Z-YJV22
Z-VLV22 |
Cross-linked polyethylene
insulation double-tape armour PVC Sheath flame retardant power cable |
Lay down is in interior, tunnel and burying
soil straightly, cable can bear pressure
and other outside force effect. |
|
Z-YJV32
Z-VLV32 |
Cross-linked polyethylene insulation steel wire Armour PVC Sheath flame retardant power cable |
Lay down is in interior, mine and water,
cable can bear pulling force suitable. |
|
Z-YJV42
Z-VLV42 |
Cross-linked polyethylene insulation thick steel wire Armour PVC Sheath flame retardant power cable |
Lay down is in interior, mine and water,
cable can bear bigger pulling force. |
|
N-YJV |
Cross-linked polyethylene insulation PVC Sheath fire resisting power cable |
Lay down is in interior、Tunnel and duct,
cable can not bear pressure and the
machinery outside force effect. |
|
|
|
|
|
|
|
|
|